High-Voltage-Testing 
						 | 
				Tunnel-Installations 
						 | 
			 
		
	 
	
	
	
		
			
				Substation-Line 
						 | 
				Horizontal-Tunnel. 
					 | 
			 
		
	 
	
	Compact Gas Insulated Transmission
	
	
	
		
			
				| 
					 mm  | 
				
					 Enclosure 
					Diameter  | 
				
					 Conductor 
					Diameter  | 
				
					 Phase 
					Spacing  | 
			 
			
				| 
					 145kV  | 
				
					 241  | 
				
					 89  | 
				
					 381  | 
			 
			
				| 
					 242kV  | 
				
					 307  | 
				
					 102  | 
				
					 457  | 
			 
			
				| 
					 362kV  | 
				
					 375  | 
				
					 127  | 
				
					 559  | 
			 
			
				| 
					 550kV  | 
				
					 508  | 
				
					 178  | 
				
					 711  | 
			 
			
				| 
					 800kV  | 
				
					 622  | 
				
					 178  | 
				
					 813  | 
			 
		
	 
	
		
			
				| 
					  Right of Way Requirement 
					 145kV CGIT Line: 1.2 meters wide 
					 242kV CGIT Line: 1.5 meters wide 
					 362kV CGIT Line: 1.8 meters wide 
					 550kV CGIT Line: 2.1 meters wide  | 
			 
		
	  
		 Design Features 
	
 Section lengths up to 18 meters 
 Bolted enclosure field joints with double o-ring seal 
  Field welded joint design available 
 Tripost conductor support insulators with particle traps 
 Corrosion resistant aluminum enclosure 
 Factory assembled and fully tested shipping assemblies 
 Experience with vertical and underground systems
					  |